Developed to overcome the problems of old outdated technology in beam detection, this motorised beam now means that beam detection can be used reliably to produce cost effective solutions for protecting large areas. Building movement and accessibility have in the past, made beam detection unreliable, difficult, time consuming to commission and hard to maintain, but now by using the advanced motorised technology of thefirebeam unreliability is no longer a problem. The ZTBEAM will self align itself to the centre of the reflector when commissioning and will automatically keep alignment with the reflector when building movement occurs. This intelligent motorisation will mean less false alarms therefore saving time, resources, reputations and ultimately money.
Connection Diagram
Features
Motorised head unit
Controller unit (mounted at low level)
Designed to comply with EN54 part 2
Compatible with most major fire panels
Very low power consumption
Uses only 3mA at all times
Additional Features
ZT-BEAM/KIT80 Mid range kit for distances between 40 and 80 metres.
ZT-BEAM/KIT100 Long range kit for distances between 80 and 100 metres.
Technical Specification
Model
ZT-BEAM
ZT-BEAM/KIT80
ZT-BEAM/KIT100
Supply Voltage
-10.2 to 30 VDC
Supply Current
3.5mA (constant current) in all operational states
Constant Current
17mA (constant current) in fast commissioning
Temperature
-10°C to +55°C
Humidity
10 to 95% RH Non-condensing
Protection Index
IP65 when suitably mounted and terminated
Dimensions
Head:
Controller:
(H) 180mm
(H) 185mm
(H) 293mm
(H) 394mm
(W) 155mm
(W) 120mm
(W) 293mm
(W) 394mm
(D) 137mm
(D) 62mm
(D) 5mm
(D) 5mm
Weight
1.1Kg
0.55g
Weight 0.8Kg
Weight 1.8Kg
Optical Wavelength
870nm
Maximum Angular Alignment
±5°
Maximum Angular Misalignment
(static not auto-aligning)
Beam Head ±0.75°
Reflector ±2°
Protection Range
5 to 40 metres
40 to 80 metres
80 to 100 metres
Alarm Sensitivity Levels
25%(1.25dB) to 50%(3dB) in 1%(0.05dB) increments (default 35% (1.87dB))
Alarm Condition
Controller Status – FIRE
Controller Red Flashing LED
Head Red Flashing LED
Alarm Relay Change Over (CO) Contact
Rating 2A @ 30 VDC
Test/Reset Features
Beam test function by controller
Alarm latching/auto-reset selectable (default auto-reset)
Alarm reset in latching mode by controller reset function, removing power for >5 seconds, apply 12 to 24 VDC to reset connections in Beam Head.
Fault Sensitivity Level
90%
Fault Condition
Obscuration drops to below the fault sensitivity level within 1 second
Power Down or Supply Voltage < 9 VDC
Commissioning modes, Pre-Alignment and Auto Alignment
Beam turned off during Beam Maintenance Time to Fault Condition adjustable, 2 to 60 seconds in 1 second increments (default 10 seconds)
Fault Indication
Controller Status – FAULT
Controller Yellow Flashing LED 1 Second
Head Yellow Flashing LED 1 Second
Fault Relay Change Over (CO) Contact
Rating 2A @ 30 VDC
Normal Condition
Obscuration level is above the Alarm sensitivity level
Controller Status – NORMAL
Controller Green Flashing LED
Programmable on/off
Head Green Flashing LED
Programmable on/off
Auto-align/Beam Contamination Compensation
Auto-align during normal operation if obscuration drops below 90% for the duration of the align time set (doesn’t effect normal operating mode)
Beam Contamination Compensation 4 hour monitoring. Compensation data available at the controller